Every grow light is bought on a number measured at full output and then operated for most of its life somewhere else. Photoperiods run twelve to eighteen hours, so a fixture sits dark for six to twelve hours a day, and during much of the lit period it is dimmed rather than at rated power. The energy meter does not care about the datasheet condition. It integrates whatever the driver draws across the whole year, including the hours when the room is dark and nobody is looking at the lamps.

The result is a systematic gap between the efficiency a facility believes it bought and the efficiency it pays for. That gap is not exotic: it comes from three ordinary mechanisms — standby consumption, no-load loss and the collapse of converter efficiency at light load — and it scales with the number of fixtures rather than with their power. A 200-fixture multi-tier room turns a 2 W idle draw into a line item worth arguing about.

Rated Efficacy Describes a Condition Nobody Runs

Energy efficacy for horticultural luminaires is quoted in micromoles of photosynthetic photon flux per joule of input energy, measured at rated power with a stabilised fixture at thermal equilibrium. It is a good comparator for the emitter-and-optics package, and a fair one when two products are measured the same way.

It is also a peak figure. A 2.9 µmol/J rating at 100 percent output says nothing about the same fixture at 30 percent output, nothing about what the driver draws with the output stage disabled, and nothing about a controller that stays awake all night. Those three conditions occupy a large share of the calendar. The rated number describes the strongest hour of the day; the bill describes all 8,760 of them.

The practical framing is that two efficiencies exist. Peak efficacy is what the specification sheet reports. Annual efficacy is the total photon delivery divided by total input energy over a year, including dark hours and dimmed hours. The second number is the one a facility can improve without changing a single fixture.

Three Losses That Do Not Appear on a Datasheet

Standby consumption is the power drawn while the fixture produces no light but remains connected and controlled. Its source is the driver’s auxiliary supply plus the control interface: a 0–10 V receiver, a DALI interface, a wireless node or a monitoring board. Figures in the field run from roughly 0.3 W per fixture for a well-designed dim-to-off driver to 1.5 W, and poorly designed units with an always-on radio can exceed 3 W. The mechanism is simple: converting mains to a low auxiliary rail at low current is inefficient, and everything downstream keeps running whether or not the LEDs do.

No-load loss is what the driver draws with its output open — the LEDs disconnected, or the output stage inhibited while the converter keeps switching. Depending on topology, that can be one to five watts of switching and magnetic loss, because the transformer core and the switching devices keep working with nowhere for the energy to go. Flyback and LLC stages behave differently here, but both can idle wastefully.

Low-load efficiency loss is the third and least visible. A switching converter is normally optimised around 60 to 100 percent of rated load, where conduction loss dominates and the design is tuned. As load falls, fixed losses — core loss, gate drive, control supply, sensing — stay constant while output shrinks, so the ratio deteriorates. A supply that reaches 92 percent at full load commonly measures 84 to 87 percent at 20 percent load, a fall of five to eight percentage points. Dimming to 20 percent therefore does not cut input power to 20 percent of rated; it cuts it to something higher.

Loss mechanism Physical cause Typical magnitude How to measure it Removable by design
Standby, dim-to-off Auxiliary supply plus control interface 0.3–1.5 W per fixture, up to 3 W True-RMS wattmeter after controller command Yes, by mains isolation
No-load Converter switching with open output 1–5 W Wattmeter with LED string disconnected Partly, by output-stage inhibit
Low-load efficiency Fixed losses against shrinking output 5–8 points lost at 20% load Comparative input/output at 4 load points Partly, by topology choice

Doing the Arithmetic: Watts, Fixtures, Hours

Three formulas cover most of the audit, and all of them are simple enough to run during a meeting.

Standby energy per year equals fixture count multiplied by standby watts multiplied by non-illuminated hours, divided by 1,000. For a 200-fixture room at 2 W each with 12 dark hours a day, that is 200 × 2 × 4,380 / 1,000 = 1,752 kWh a year. At an industrial tariff of 0.20 per kWh, roughly 350 per year, from fixtures that are producing nothing at the time.

Dimmed-hour loss is a second term. Take a 30 kW group of fixtures running at 25 percent output for four hours a day, with driver efficiency of 92 percent at full load falling to 85 percent at that setting. Output is 7.5 kW; input at 92 percent is 8.15 kW and at 85 percent is 8.82 kW, so the penalty is about 0.67 kW, or 2.7 kWh a day for the group. Over a year that is roughly 980 kWh per group, and eight such groups put the total near 7,800 kWh — several times the standby figure, and entirely invisible on a datasheet.

The third term is the comparison that decides a purchase. Standby cost scales with fixture count and dark hours: N × W × h_dark. Rated-power efficiency differences scale with delivered power and lit hours: P × h_lit × Δη. A fixture rated three percent lower in efficacy but drawing 0.3 W at standby can beat a higher-rated unit drawing 3 W, once the array is large and the dark period is long. Running both terms in the same units, kWh per year, settles arguments that otherwise stay qualitative.

The scaling rule deserves emphasis because it inverts an intuition. Standby loss is independent of fixture wattage, so a design using many small fixtures — the normal arrangement on multi-tier racks — pays proportionally more than a design using a few large ones for the same installed photon capacity. A 100 W fixture at 2 W standby loses two percent of its rated draw while idle; the same 2 W on a 40 W fixture loses five percent.

Benchmarks and Where the Rules Come From

There is no horticultural standby regulation, so the useful approach is to borrow a reference and label it honestly as a benchmark rather than an obligation.

The European Commission’s ecodesign framework sets limits for standby and off modes on household and household-like equipment: no more than 0.3 W in off mode, 0.5 W in standby, and 2.0 W for networked standby where a network connection must be maintained. The scope is domestic appliances, not commercial horticultural luminaires, so a grow light is not obliged to comply. The numbers are still the right order of magnitude for a purchase clause, because they represent what a well-designed low-power auxiliary supply can achieve — see the European Commission’s standby and networked standby product page for the current limits and their scope.

The second reference is measurement rather than regulation. Lawrence Berkeley National Laboratory has documented standby power across appliance categories for decades, and its standby power research programme is the standard source for the observation that standby draws of one or two watts per unit become material only when multiplied across a building. That is precisely the multiplier a multi-tier grow room supplies.

The honest conclusion from both: 0.5 W per fixture is achievable and worth writing down; 3 W per fixture is a design choice somebody made and nobody costed.

Measuring It Without a Laboratory

The instrument is a true-RMS power meter with 0.1 W resolution at low readings, ideally with logging, plus a clamp meter for verifying that no parallel load shares the circuit. A plug-in energy monitor of the domestic type usually fails at the bottom of its range, where the interesting numbers are.

The procedure has four steps. Record input power at full output as a baseline. Then step the controller down through 50, 25 and 10 percent, allowing a minute at each setting for the driver to settle, and record input power alongside the commanded level. Then send the off command from the controller — dim-to-off, schedule end, or network command — and read again after two minutes. Finally, isolate the controller from the driver, energise only the driver, and repeat, so that controller standby and driver standby are reported as separate numbers. Lumped figures cannot be acted on, because the remedy differs: a controller can be put on a timer or a contactor, a driver cannot.

Two traps produce most of the bad data. First, a meter reading volt-amperes rather than watts overstates a low-power-factor standby load by a factor of 1.5 to 2, so a fixture that genuinely draws 0.8 W can appear to draw 1.6 VA. Second, inrush current at energisation is not steady-state consumption; a reading taken in the first second after switching records a surge that lasts milliseconds.

Repeat the survey on a sample across batches and, where possible, across firmware revisions. Auxiliary supplies and control boards change between production runs without any change to the model number, and standby behaviour is one of the parameters most likely to move.

Dimming Architecture Decides the Standby

Three shutdown strategies exist, and the choice between them determines whether the standby term exists at all.

Dimming to zero through the control interface — the standard 0–10 V or DALI dim-to-off behaviour — leaves the driver’s mains input live and its auxiliary supply running. The fixture is dark and still consuming. Nothing in the control signal removes mains voltage, and no amount of protocol configuration changes that, because the relay that would disconnect the input is not there.

Switching mains at a contactor or relay removes the standby almost entirely: the only continuous load is the coil of the contactor itself while it is energised, and once de-energised the fixture draws nothing. The cost is granularity. One contactor serves a group, so all fixtures in that group switch together, which is acceptable where a photoperiod boundary is the only event that matters and unacceptable where zones run independent recipes.

Networked standby is the third case. A fixture with a mesh node, a wireless radio or an on-board web server must keep that node alive to receive commands, which is why networked standby limits are looser than plain standby limits. The capability is real — per-fixture addressing, dimming curves, fault reporting — but it is paid for continuously, in every fixture, all night.

A decision rule follows: where the photoperiod is stable and a zone holds 50 fixtures or more, a contactor upstream of the group usually pays for itself quickly, and the control system can still dim within the lit window. Where zones change recipes frequently and per-fixture control is a genuine operational requirement, keep the always-on architecture and instead write the standby wattage into the specification as a hard limit.

Where Standby Review Changes the Layout Decision

The multi-tier rack is where this analysis has the most leverage, and also where it is most often skipped. Rack designs tend to optimise photons per square metre of canopy and per capital unit, using many modest fixtures at short mounting distances. That choice multiplies both the fixture count and the standby term, so two layouts delivering identical PPFD at the canopy can differ materially in annual energy.

The evaluation is straightforward once the terms are on the same footing. For each candidate layout, list fixture count, rated input power, measured standby power per fixture, dark hours and dimmed-hour profile. Convert everything to kWh per year, add the three terms, and divide by annual photon delivery. The layout that wins on that ratio is not always the one that wins on rated efficacy, and the difference is usually large enough to matter at the procurement stage.

Koray Lights builds horticultural luminaires and has supplied controlled-environment growers for 17 years. Standby power, no-load loss and part-load efficiency figures for individual models are not published by the manufacturer, so they should be requested as measured values at 100, 50, 25 and 10 percent load, with the dim-to-off state reported separately from the driver’s no-load state.

Dimension Comparison: Load-Region Efficiency

The table below is the audit template. Each row is a separate operating state with its own expected range, its own share of annual energy and its own acceptance test.

Operating state Typical performance Share of annual energy Removable? Acceptance test
Full output, 100% load 88–93% driver efficiency Largest single share No, it is the work Input/output at rated power
Dimmed, 50% load 1–3 points below peak Moderate No Input power at commanded level
Dimmed, 20–25% load 5–8 points below peak Small per hour, large per year Partly, by topology Four-point efficiency curve
Standby, dim-to-off 0.3–1.5 W per fixture Grows with fixture count Yes, by mains isolation Wattmeter after off command
No-load, output open 1–5 W Small, unless faults are frequent Partly, by inhibit Reading with LED string open
Mains-disconnected 0 W Zero Not applicable Contactor verification

Conclusion

The energy a grow light consumes is not one number but a profile. Rated efficacy describes the top of that profile, at thermal equilibrium, at full output, with the lamp producing light. Standby power, no-load loss and low-load efficiency describe the rest of it, and they share a property that makes them easy to ignore: none of them appears on a specification sheet, and all of them appear on the bill.

The corrective actions are cheap and mostly organisational. Measure the four operating states, report controller and driver standby separately, put a contactor where the photoperiod is stable and the group is large, and write a standby ceiling into the purchase order alongside the efficacy figure. A facility that compares fixtures on annual kWh per mole of delivered photons rather than on peak micromoles per joule will usually find that the cheapest energy is the energy drawn by a fixture that is genuinely disconnected.

Frequently asked questions

Do LED grow lights use power when they are switched off?

Yes, if they are switched off by a control command rather than by removing mains voltage. Dim-to-off, schedule end and network off commands leave the driver’s input live so its auxiliary supply and control interface keep running, typically drawing 0.3 to 1.5 W per fixture. Only a contactor, relay or breaker upstream of the driver reduces that to zero.

What is no-load loss on a grow light driver?

No-load loss is the power a driver consumes with its output open or inhibited while the converter keeps switching. It is typically one to five watts depending on topology, since the transformer core and switching devices continue to dissipate energy with no load to deliver it into. It is measured with the LED string disconnected and the driver energised.

Why does driver efficiency drop when I dim to 20 percent?

Because a switching converter is designed around 60 to 100 percent of rated load, where conduction loss dominates. At light load the fixed losses — core loss, gate drive, control supply and sensing — stay roughly constant while output shrinks, so the ratio of output to input falls. A 92 percent supply often measures 84 to 87 percent at 20 percent load.

Is 2 W of standby power per fixture actually significant?

It depends on fixture count and dark hours, not on the wattage alone. Two watts over 4,380 dark hours is 8.8 kWh per fixture per year, so 200 fixtures consume about 1,752 kWh a year while producing no light. On a rack with many small fixtures the same 2 W represents a larger fraction of rated draw than on a few large ones.

Should I switch grow lights with a contactor instead of dim-to-off?

Use a contactor where the photoperiod is fixed and a zone holds enough fixtures for the saving to justify the hardware, because it removes standby draw almost completely. Keep dim-to-off or networked control where zones change recipes often or per-fixture addressing is needed, and specify a standby wattage ceiling instead. The two approaches can coexist: a contactor for the group, dimming for the lit window.